Products & Applications
PRODUCTSIntelligent lighting control system
Location Position:Home > Products & ApplicationsDK2000-CC0206 Curtain module

2-1 Product Overview:
DK2000-CC0206 is a two-loop curtain controller with its own man-machine interface. It uses efficiency relay output and output rated current 6A to meet the operation requirements of most curtain actuators. Two groups of curtain control output, each group positive and negative rotation to realize the electrical interlock of software and hardware, to ensure electrical safety.
2-2 Product Functions and Features:
1. All Chinese LCD display, menu type Chinese interface, so that you can combine the function keys, very convenient for parameter setting and scene call and other functions.
2. Two groups of curtain control output, curtain load motor power 12V~220VAC/DC is not restricted.
3. It has the function of scene timely sequence control. 12 scenes and 1 sequence can be customized by users.
4. Each group of curtain control output can be directly controlled through the key to open and close the curtain.
5. According to illuminance, outdoor temperature to achieve automatic control function, but need to add the corresponding sensor (illuminance and temperature sensor) can be realized.
6. Reserve two groups of switching quantity DI and two groups of analog quantity AI signal input ports, which can flexibly realize specific functional requirements according to user needs.
2-3 Networking diagram of curtain module
2-4 Product specifications and technical parameters
Power consumption: DC 24V / 6VA
Environment/Use: -20 to 60°C; 10 to 85% RH
Storage environment: -20 to 90 °C; Less than 90% RH
Man-machine interface: 12864LCD screen, "Menu/confirm", "up", "down", "left" and "right" buttons
Microprocessor: ARM series single chip microcomputer watchdog device automatic return.
Communication mode: 1xRS-485 1/2 duplex/Modbus RTU Protocol
Communication rate: 9600~76.8k bps (factory/recommended 9600 bps)
Maximum communication distance: 4000 ft (1.2 km)
Communication signal input: RS485 Modbus RTU
Communication address setting range: Up to 16, that is, a panel can be connected to a maximum of 16 controllers
Output specification: Two groups of curtain control output, each group rated current 6A
Communication signal connection head: 5PIN terminal
Dimensions: 162 mm x 90 mm x 63mm
Installation: Standard DIN35 electric track
Weight: 580 g
2-5 Product size drawing:
2-6 Schematic diagram of product wiring:
2-7 Hardware description of curtain module:
DK2000-CC0206 Curtain module hardware description |
|||
project |
name |
function |
remarks |
1 |
LCD screen |
Man-machine interface, display and set related functions |
|
2 |
Press Up |
Adjust the value/status of a set parameter |
|
3 |
Press Down |
|
|
4 |
Key Left |
Move the menu and select the desired menu item |
|
5 |
Key Right |
|
|
6 |
Press Enter |
The 'Confirm' button, when a menu or option is selected, will be backfired. |
|
7 |
2 sets of curtain loop manual adjustment |
? : Reversal,? : Forward turn,N/V-: zero line or common end |
|
8 |
Wiring terminals DC24V+ and - |
Power DC24V input |
Power Power indicator. The indicator is on during normal operation |
9 |
Wiring terminal D+,D-,GND |
RS485 communication cable. D+ is connected to the communication line; D- Connect the communication line negative; GND connects to the masking layer. |
Tx and Rx indicators. When the communication is normal, the two indicators blink |
10 |
Wiring terminals DI1, DI2, COM |
Passive switch input DI1,DI2, COM is the common terminal. |
When the switch quantity is closed and input, the corresponding indicator of DI1 and DI2 will light up |
11 |
Terminal AI1,AI2,AIG |
Analog signal input AI1,AI2, AIG is the common end. Input sources can be 0-10v,4-20mA, or NTC sources. |
Select source input mode by changing JP route position |
12 |
Wiring terminals N/V-, L/V+ |
Supply power to 2 sets of curtain output circuits |
|
13 |
Terminal N/V- |
Provide 2 sets of curtain output |
|