Compact intelligent circuit breakers & intelligent residual-current-operated circuit breakers

  
1. Model and Specifications

2. Technical Parameters


3.Functional Features

Note: Phase-loss protection / three-phase imbalance protection: applicable only when used in conjunction with a three-phase product and gateway to enable four-way remote monitoring functionality.


4. Characteristic Parameters

Remarks:
1. Specified time – 1.13: No operation within 1 h (2 h) after power-on; 1.45: Operation within 1 h (2 h) after power-on; for products rated ≥80 A, the time is 2 h;
2. Prescheduled time – 2.55 In: act when In ≤ 32 A (1–60 s); act when In> 32 A (1–120 s).
3. Prescribed timing – Type B: 3 In; Type C: 5 In; Type D: 10 In. No activation occurs within 100 ms after power-on; Type B: 5 In; Type C: 10 In; Type D: 15 In. Activation occurs within 100 ms after power-on;
4. Prescheduled timing – Type C: 5In/D: Type 10In; no actuation within 100 ms of power-on; Type C: 10In/D: Type 15In; actuation within 100 ms of power-on.

5. Technical Description
★1.1 The product width for a P+N circuit with a leakage protection relay occupies only 1 × 18 mm and occupies 3 P-positions; a 3P+N configuration occupies 5 P-positions and 90 mm.
★2. Dual protection using a bimetallic strip and electronic components ensures that the intelligent circuit breaker retains its protective function even when the software fails.
★3. AI Load Recognition Technology: The product features high-frequency waveform recording and AI self-learning capabilities, enabling it to identify different load types on the same circuit based on the waveform; this allows the circuit to be configured with a load whitelist, thereby specifying which loads are permitted.
★4. Automatic 485 address assignment for intelligent circuit breakers.
5. The intelligent circuit breaker complies with internationally unified standards; its configurations include 1P,2P,3P,4P, (leakage protection) 1P+N, and (leakage protection) 3P+N. It features standard rail-mounted installation and plug-and-play communication; its interior integrates a built-in mechanical power control device and a digital control chip.
6. Integrated built-in power supply design: No additional power supply module is required, thereby eliminating the risk of protection function failure caused by failures in an external power supply.
7. Customizable rated current function. For 1P/2P/3P/4P products rated at 63 A, the adjustable range is 1–63 A (the frame rating can reach 100 A, but this requires customization: 70 A, 80 A, or 100 A); for 1P+N and 3P+N products rated at 63 A, the adjustable range is likewise 1–63 A. The JLIB3LE is available in two versions—leakage protection and leakage monitoring—and the rated current of the corresponding smart power management module can be customized based on the actual line load and protection requirements.
8. It can collect fault information—including overvoltage, undervoltage, overload, overtemperature, and leakage current—in real time and report it to the system in real time.
9. Ground fault protection: When the monitored residual current reaches 18–26 mA, the circuit will automatically open. When the line leakage current reaches 30 mA, the circuit breaker provides a 0.04s power-off protection period (applicable only to circuit breakers equipped with ground fault protection). In industrial settings, when the line leakage current reaches 100 mA or 300 mA, the circuit breaker provides a 0.1s power-off protection period (applicable only to circuit breakers equipped with ground fault protection).
10. Enables real-time monitoring of electrical parameters such as voltage, current, temperature, leakage current, active power, reactive power, active energy, and power factor;
11. Remote control. Remote switching of the connected circuit can be performed via a mobile phone or computer-based management platform.
12. Overvoltage protection and self-resetting function. When the voltage exceeds the set overvoltage protection threshold, the intelligent circuit breaker automatically opens; once the voltage returns to normal, the intelligent circuit breaker automatically closes approximately 20s later. Setting range: 270–280 V. The three-stage early-warning circuit breaker allows the overvoltage warning threshold (default: 250 V), overvoltage alarm threshold (default: 260 V), and overvoltage protection threshold (default: 275 V) to be configured in separate sections, with an adjustable range of 240 V–280 V. After voltage abnormality protection is activated, once the voltage returns to normal, the circuit breaker automatically restores power within 20s.
13. Meet or exceed overcurrent protection requirements: at 10% above the rated current, disconnect after 10 seconds; at 35% above the rated current, disconnect after 5 seconds; at 100% above the rated current, disconnect after 1 second.
14. The local fault indicator displays the operating status of the circuit, including normal operation, fault, and alarm status, and can indicate the type of fault (current, voltage, leakage current, temperature).
15. Equipped with a local safety lock protection function. Once the local lock is released, neither the local nor the remote system can be closed, ensuring that maintenance personnel are not exposed to live-line operations caused by another person inadvertently restoring power.
16. Gateway scheduling feature. Allows users to customize the circuits requiring scheduled operation, the switching time, and the cycle period. Schedule automatic switching via the web interface or app to achieve automated switching control, with the gateway issuing the corresponding commands.
17. Electric energy metering functionality. (JLIB3, JLIB3LE) provides Class 2 active energy metering accuracy; (JLIB5, JLIB5LE) provides Class 1 active energy metering accuracy. The current and historical electricity consumption for each circuit can be viewed via a mobile phone or computer-based management platform.
18. Overtemperature protection function. Overtemperature protection function (circuit breakers and residual-current circuit breakers): The overtemperature protection threshold for circuit breakers and residual-current circuit breakers can be set; by default, at 80 °C, the three-stage warning thresholds for residual-current circuit breakers can be independently configured: warning at 65 °C, alarm at 75 °C, and trip at 90 °C.
19. Cable temperature can be monitored. The temperature probe can be positioned at a customizable location.
20. Equipped with a 485 communication interface.
21. Use an independent internal power supply to ensure that power supply failure does not affect the normal operation of other products.
22. Utilize the national standard guide-rail clip installation method for a simple and convenient replacement.
23. Undervoltage protection and self-resetting function: The three-stage early-warning circuit breaker allows the undervoltage warning level (default: 190 V), undervoltage alarm level (default: 180 V), and undervoltage protection level (default: 170 V) to be set separately, with an adjustable range of 150 V–200 V. After voltage abnormality protection is activated, the circuit breaker will automatically restore power within 20s once the voltage returns to normal. When the voltage exceeds the overvoltage setpoint or falls below the undervoltage setpoint, the intelligent circuit breaker will automatically open; when the voltage returns to normal, the intelligent circuit breaker will automatically close approximately 20s later.
24. Power limitation: Supported.
25. Leakage protection: A three-stage warning circuit breaker allows the leakage warning level (20 mA), leakage alarm level (25 mA), and leakage protection level (30 mA) to be set independently for each section; the adjustable range is 5–300 mA, and the leakage protection response time is less than 0.05s.
26. Overload protection: The line's rated current can be customarily set within the current range of the enclosure class; when the instantaneous current exceeds 1.13 times the set current, the circuit breaker does not trip; when it exceeds or equals 1.13 times the rated current, the circuit breaker automatically trips after 60 minutes; when it exceeds or equals 1.45 times the rated current, the trip time can be set, with a default automatic trip time of 15 seconds; when the circuit breaker trips, a corresponding warning message is reported. When the current exceeds or equals 2 times the rated current or higher, the circuit breaker trips according to the time setting specified on the double-kink characteristic curve.
27. Short-circuit protection: the circuit is immediately disconnected when a short circuit occurs, ensuring electrical safety. The breaking capacity is greater than 6 kA (for currents exceeding 63 A); the breaking capacity is 10 kA (for currents up to and including 63 A).
28. Phase-loss protection: when the phase voltage falls below 120 ± 5% V, phase-loss protection is triggered, automatically disconnecting the circuit to ensure electrical safety.


For any further specific details, please feel free to contact our customer service representatives; we will be delighted to assist you.